| AWG | Diameter (mm) | Area (mm²) | Resistance (Ω/km) | Ampacity — Conduit (A) | Ampacity — Free Air (A) | Typical Use |
|---|
- All ampacity values based on NEC 2023 Table 310.16 for 75°C rated copper conductors
- Always apply a 125% safety factor for continuous loads (loads on for 3+ hours) per NEC 210.19
- This calculator is a reference tool only — all electrical installations must be designed by a licensed electrician or electrical engineer and inspected per local codes
- Voltage drop not calculated here — for runs over 100 feet, upsize wire to keep voltage drop below 3% (NEC recommends ≤5% total)
- Aluminum conductors have lower ampacity — use separate tables for aluminum wiring
- Never rely solely on this calculator for life-safety electrical design
What Is Wire Ampacity?
Ampacity is the maximum continuous current a conductor can carry without exceeding its temperature rating under specific installation conditions. It is not a fixed property of the wire alone — ampacity depends on the conductor size, insulation temperature rating, ambient temperature, and how many other current-carrying conductors are bundled together. Selecting the wrong wire gauge is a primary cause of electrical fires and is a life-safety issue that must be taken seriously.
AWG Quick Reference Table
| AWG | Dia (mm) | 60°C Amp | 75°C Amp | 90°C Amp | Resistance (Ω/1000ft) | Common Use |
|---|---|---|---|---|---|---|
| 14 | 1.63 | 15A | 20A | 25A | 2.525 | 15A branch circuits |
| 12 | 2.05 | 20A | 25A | 30A | 1.588 | 20A branch circuits |
| 10 | 2.59 | 30A | 35A | 40A | 0.999 | 30A circuits, dryers |
| 8 | 3.26 | 40A | 50A | 55A | 0.628 | 40–50A, EV chargers |
| 6 | 4.11 | 55A | 65A | 75A | 0.395 | Subpanels, hot tubs |
| 4 | 5.19 | 70A | 85A | 95A | 0.249 | Large appliances |
| 2 | 6.54 | 95A | 115A | 130A | 0.156 | Service entrance |
| 1/0 | 8.25 | 125A | 150A | 170A | 0.098 | 200A service |
Source: NEC Table 310.16 — Copper conductors, not more than 3 current-carrying conductors in raceway, 30°C ambient.
Worked Examples
Example 1 — Standard 20A Kitchen Circuit
What wire gauge is needed for a 20A kitchen appliance circuit with THWN-2 insulation in a 30°C environment?
Example 2 — High Temperature Environment (Derating Required)
A circuit in a commercial kitchen near cooking equipment sees 50°C ambient. The load is 18A continuous. What wire gauge is required with THWN insulation?
Example 3 — Bundled Conductors in Conduit
Six 12 AWG THWN current-carrying conductors are installed in the same conduit. What is the derated ampacity of each conductor?
Example 4 — Long Run Voltage Drop Check
A 20A, 120V circuit runs 150 feet to a workshop. Is 12 AWG adequate for voltage drop (NEC recommends max 3%)?
Real World Applications
Common Mistakes Engineers Make
Frequently Asked Questions
Yes, aluminum wire is code-compliant and widely used for service entrances, feeders, and large branch circuits. Aluminum has about 61% the conductivity of copper, so you need a larger gauge (typically 2 sizes larger) for the same ampacity. Critical requirements: use only CO/ALR rated devices and connectors, apply anti-oxidant compound at all connections, and never connect aluminum directly to copper without an approved connector. Aluminum branch circuit wiring (smaller than 4 AWG) in homes has been associated with fire hazards when improperly installed.
THHN is rated 90°C in dry locations. THWN is rated 75°C in wet or dry locations. Most wire sold today is dual-rated THHN/THWN-2. NM-B (Romex) is a cable assembly containing multiple conductors with an outer plastic jacket, rated 60°C, used for residential branch circuit wiring in dry locations only — not suitable for conduit, wet locations, or exposed installations.
Motor branch circuit conductors are sized at 125% of the motor’s Full Load Amps (FLA) from NEC Table 430.250 (not the nameplate current) per NEC 430.22. For example, a 10 HP, 230V, 3-phase motor has FLA = 28A. Branch circuit conductor = 28 × 1.25 = 35A minimum — requiring 8 AWG copper minimum. Overcurrent protection (breaker/fuse) is sized separately and may be much larger to allow for motor starting inrush.
A 50A EV charging circuit requires a minimum 6 AWG copper conductor per NEC Table 310.16 (65A rated at 75°C, derated for continuous load: 50A × 1.25 = 62.5A). However, if the run is longer than 75–100 feet, voltage drop analysis may require 4 AWG. The charging circuit breaker should be 60A (next standard size above 50A continuous load calculation).
